Schedule 40 Rigid PVC Piping Systems


SCHEDULE 40 - DIMENSIONS

 


Harvel Clear pipe and fittings are manufactured in IPS sizes to Schedule 40 dimensions for optimum performance. This provides sufficient wall thickness for most pressure applications without jeopardizing clarity. As a rigid PVC piping, Harvel Clear PVC maintains its integrity in harsh environments. It is suitable for use in both positive and negative pressure applications (i.e., vacuum service).

As with all schedules of thermoplastic pipe, pressure rating is dependent on the pipe diameter selected as well as the operating temperature of the system. As temperatures rise, the pressure rating of the system decreases. Smaller diameter piping can withstand higher pressures than large diameter piping. Refer to the table below for dimensions, tolerances and pressure ratings.

Dimensions and Pressure Ratings

Nominal Pipe Size (in)
O.D.
Average I.D.
Min. Wall
Nominal Wt./Ft.
Max. W.P. PSI**

1/4"

0.540

0.344

0.088

0.086

390

3/8"

0.675

0.473

0.091

0.115

310

1/2"

0.840

0.602

0.109

0.170

300

3/4"

1.050

0.804

0.113

0.226

240

1"

1.315

1.029

0.133

0.333

220

1-1/4"

1.660

1.360

0.140

0.450

180

1-1/2"

1.900

1.590

0.145

0.537

170

2"

2.375

2.047

0.154

0.720

140

2-1/2"

2.875

2.445

0.203

1.136

150

3"

3.500

3.042

0.216

1.488

130

3-1/2"

4.000

3.521

0.226

1.789

120

4"

4.500

3.998

0.237

2.118

110

6"

6.625

6.031

0.280

3.733

90

6" X 1/8

6.625

6.335

0.110

1.647

45

8"

8.625

7.942

0.322

5.619

80

10"

10.750

9.976

0.365

7.966

70

12"

12.750

11.889

0.406

10.534

70


 

Critical Collapse Pressure

Pipe Size (in) psi @ 73°F

1/4

7504

3/8

3714

1/2

3255

3/4

1722

1

1399

1-1/4

767

1-1/2

554

2

327

2-1/2

431

3

279

3-1/2

211

4

169

6

84

8

57

10

43

12

35

De-rating Factor

Operating Temp °F De-rating Factor

73

1.00

80

0.88

90

0.75

100

0.62

110

0.51

120

0.40

130

0.31

140

0.22

 

 
 

©2008 Harvel Plastics, Inc. • 300 Kuebler Road, Easton, PA 18040 • 610-252-7355 • Fax: 610-253-4436