SDR SERIES 13.5, 21, 26, 41 - TEMPERATURE DERATING

 

Operating Temp (°F)  De-Rating Factor

The pressure ratings given are for water, non-shock, @ 73°F. The following temperature de-rating factors are to be applied to the working pressure ratings (W.P.) listed when operating at elevated temperatures.

Multiply the working pressure rating of the selected pipe at 73°F, by the appropriate de-rating factor to determine the maximum working pressure rating of the pipe at the elevated temperature chosen.

EX: SDR 21 @ 120°F = ?
200 psi x 0.40 = 80 psi max. @ 120°F

THE MAXIMUM SERVICE TEMPERATURE FOR PVC IS 140°F

Solvent cemented joints should be utilized when working at or near maximum temperatures. Harvel Plastics does not recommend the use of PVC for threaded connections at temperatures above 110°F; use flanged joints, unions, or roll grooved couplings where disassembly is necessary at elevated temperatures.

Threading of SDR Series pipe is not a recommended practice due to insufficient wall thickness.
Chemical resistance data should be referenced for proper material selection and possible de-rating when working with fluids other than water.

Refer to Harvel Plastics 112/401 Product Bulletin for chemical resistance and installation data. Pipe listed is manufactured in strict compliance with ASTM D2241

 

 
 

©2008 Harvel Plastics, Inc. • 300 Kuebler Road, Easton, PA 18040 • 610-252-7355 • Fax: 610-253-4436