PVC Pipe Schedule 80

Nom. Pipe Size (in) O.D. Average I.D. Min. Wall Nom. Wt./Ft. Max. W.P. PSI**
1/8" .405 .195 0.095 0.063 1230
1/4" .540 .282 0.119 0.105 1130
3/8" .675 .403 0.126 0.146 920
1/2" .840 .526 0.147 0.213 850
3/4" 1.050 .722 0.154 0.289 690
1" 1.315 .936 0.179 0.424 630
1-1/4" 1.660 1.255 0.191 0.586 520
1-1/2" 1.900 1.476 0.200 0.711 470
2" 2.375 1.913 0.218 0.984 400
2-1/2" 2.875 2.290 0.276 1.500 420
3" 3.500 2.864 0.300 2.010 370
3-1/2" 4.000 3.326 0.318 2.452 350
4" 4.500 3.786 0.337 2.938 320
5" 5.563 4.768 0.375 4.078 290
6" 6.625 5.709 0.432 5.610 280
8" 8.625 7.565 0.500 8.522 250
10" 10.750 9.493 0.593 12.635 230
12" 12.750 11.294 0.687 17.384 230
14" 14.000 12.410 0.750 20.852 220
16" 16.000 14.213 0.843 26.810 220
18" 18.000 16.014 0.937 33.544 220
20" 20.000 17.814 1.031 41.047 220
24" 24.000 21.418 1.218 58.233 210

** The Pressure ratings shown are for water, non-shock, @ 73°F with plain end pipe. Threaded pipe requires a 50% reduction in the pressure ratings stated. Appropriate temperature de-rating factors must be applied to determine the maximum allowable pressure when working at elevated temperatures greater than 73°F.

Derating Factor

Operating Temp (°F) De-Rating Factor
73 1.00
80 0.88
90 0.75
100 0.62
110 0.51
120 0.40
130 0.31
140 0.22